| Datasheet |
MOD 10KTL3-X |
| Input data (DC) |
|
| Max. recommended PV power (for module STC) |
15000W |
| Max. DC voltage |
1100V |
| Start voltage |
200V |
| Nominal voltage |
580V |
| MPPT voltage range |
140V-1000V |
| No. of MPP trackers |
2 |
| No. of PV strings per MPP tracker |
1 |
| Max. input current per MPP tracker |
13A |
| Max. short-circuit current per MPP tracker |
16A |
| Output data (AC) |
|
| AC nominal power |
10000W |
| Max. AC apparent power |
11000VA* |
| Nominal AC voltage(range*) |
|
| AC grid frequency(range*) |
|
| Max. output current |
16.7A |
| Adjustable power factor |
0.8leading…0.8lagging |
| THDi |
<3% |
| AC grid connection type |
3W+N+PE |
| Efficiency |
|
| MAX. efficiency |
98.60% |
| European efficiency |
98.10% |
| MPPT efficiency |
99.90% |
| Protection devices |
|
| DC reverse polarity protection |
Yes |
| DC Switch |
Yes |
| AC/DC surge protection |
Type II / Type II |
| Insulation resistance monitoring |
Yes |
| AC short-circuit protection |
Yes |
| Ground fault monitoring |
Yes |
| Grid monitoring |
Yes |
| Anti-islanding protection |
Yes |
| Residual-current monitoring unit |
Yes |
| String fault monitoring |
Yes |
| AFCI protection |
Optional |
| General data |
|
| Dimensions (W / H / D) |
425/387/178mm |
| Weight |
15kg |
| Operating temperature range |
-25°C+60°C |
| Noise emission (typical) |
≤35 dB(A) |
| Nighttime power consumption |
< 1W |
| Topology |
Transformerless |
| Cooling |
Natural convection |
| Protection degree |
IP66 |
| Relative humidity |
0~100% |
| Altitude |
4000m |
| DC connection |
H4/MC4(Optional) |
| AC connection |
Connector |
| Display |
OLED+LED/WIFI+APP |
| Interfaces: USB/RS485/WIFI/GPRS//LAN/RF |
yes/yes/Optional/Optional/Optional/Optional |
| Warranty: 5 / 10 years |
Yes/Optional |
| CE, VDE0126, Greece, EN50549, C10/C11, UTE C 15-712, IEC62116, IEC61727, IEC 60068, IEC 61683, CEI0-21, N4105, TOR Erzeuger |